ZN39-40,5/1250A skuffet høyspent vakuumbryter i innbyrdet skap
Contact Info
- Adresse:Xiangyang Industrial Zone, Liushi Town, Yueqing City, Postnr:
- Kontakt: 李经理
- Tlf:15167417505
- E-post:864640886@qq.com
Andre produkter
ZN39-40.5(35)KV-type indoor high-voltage vacuum circuit breakers (alias: 35kV indoor vacuum switch), suitable for three-phase AC 50Hz power systems with a rated voltage of 40.5kV, comply with the GB1984 "AC High-Voltage Circuit Breakers" standard. This product can be used in conjunction with JYN1-35 and GBC-35 switchgear, including components such as isolated trolley and PT trolley.
The circuit breaker adopts a trolley-type structural design. The arc extinguishing chamber is supported by double insulators and an insulating plate, and is suitable for installation in trolley-type switchgear. Its operating mechanism can be optionally equipped with CD10-III electromagnetic mechanism or CT19N spring mechanism, and is equipped with an interlocking device to realize forced mechanical locking, meeting the "five-prevention" functional requirements of the switchgear. There are multiple specifications such as ZN39-40.5/630-25 to ZN39-40.5/2500A-31.5KA.
ZN39-40.5 series indoor high-voltage vacuum circuit breakers are indoor devices for three-phase AC 50Hz with a rated voltage of 40.5kV. The overall design is a trolley-type structure, and each arc extinguishing chamber is supported by two insulators and an insulating plate, making it easy to install in trolley-type switchgear. The circuit breaker can be equipped with electromagnetic and spring operating mechanisms. The trolley is equipped with grounding contacts to ensure reliable grounding when the trolley is in the working position or test position.
ZN39-40.5 series indoor high-voltage vacuum circuit breakers are high-voltage power distribution equipment with a rated voltage of 40.5kV for three-phase AC 50Hz, which are widely used in power systems of power plants, substations and industrial and mining enterprises for power reception, control and protection.
The circuit breaker adopts a trolley-type structural design, which is convenient for matching with switchgear models such as JYN1-35 and GBC-35, and can include components such as isolated trolley and PT trolley. Its arc extinguishing chamber is supported by two insulators and an insulating plate, with stable overall structure, reasonable layout and convenient installation and debugging. The circuit breaker adopts air insulation, which meets the requirements of air insulation distance and creepage distance under normal operating conditions.
The following are the main technical specifications of the ZN39-40.5 series circuit breakers:
Rated voltage: 40.5 kV.
Rated current: covers multiple levels such as 630A, 1000A, 1250A, 1600A, 2000A, 2500A.
Rated short-circuit breaking current: 25 kA or 31.5 kA.
Rated short-circuit closing current: 63 kA or 80 kA.
Rated peak withstand current: 63 kA or 80 kA.
Rated short-time withstand current: 25 kA or 31.5 kA, with a duration of 4 seconds.
Rated operating sequence: O -0.3s- CO -180s- CO.
Mechanical life: 10000 times.
Rated short-circuit breaking times: 30 times.
Rated insulation level:
1-minute power frequency withstand voltage: 95 kV (pole to ground, between poles and between breaks).
Lightning impulse withstand voltage: 185 kV (pole to ground, between poles and between breaks).
This circuit breaker can be optionally equipped with electromagnetic operating mechanism (CD10-II or CD10-III type) or spring operating mechanism (CT19N type), supporting AC, DC or manual operation. The product is equipped with a set of mechanical interlocking devices. When used with switchgear, it can realize the "five-prevention" functional requirements of the switchgear through forced mechanical locking to ensure operational safety.
To ensure the normal operation of the equipment, its working environment must meet the following basic conditions:
Ambient temperature: -25℃ to +40℃ (storage and transportation allowable temperature is -30℃).
Altitude: no more than 1000 meters.
Air humidity: the daily average relative humidity is not more than 95%, and the monthly average relative humidity is not more than 90%.
Other requirements: the installation site should be free of fire and explosion hazards, no serious pollution, chemical corrosion and severe vibration, and the seismic intensity should not exceed 8 degrees.
Product application and compatibility
ZN39-40.5 series circuit breakers are suitable for places requiring frequent operation. In addition to being used as protection and control units for new projects, they are also commonly used for oil-free transformation of oil-minimum circuit breakers in original switchgear models such as JYN1-40.5 and GBC-40.5.